Modular vs. Traditional Cleanroom Panels: A Comprehensive Comparison

Jason Peng, an engineer at Deiiang Company

  • Author:Jason Peng

  • Cleanroom Engineering Technology Manager of Deiiang Company.

    Product R&D Manager of GDC Inc. Cleanroom Equipment Manufacturing Company.

    Executive Director of Guangdong Cleanroom Industry Association of China.

    Engaged in R&D of related products for 15 years, with rich relevant technical experience

  • 2025-11-29  |  Visits:

The implementation of the two systems addresses different issues altogether. The earnest distinction is explained as follows: when one seeks speed, changeover, and phased renovations over a cleanroom lifecycle, modular cleanroom panels should be used.

Where a permanent design and complicated capacity integration are wanted, site-built construction is the preferred option. Modular vs traditional cleanroom panels is not a matter of better quality; it is a matter of lifecycle fit.

For a pharmaceutical plant revalidated on a 5–8 year schedule, modular cleanroom panels generally lead to the lowest total cost of ownership. For a semiconductor process plant where equipment stays in place for a longer duration, site-built panels are considered the best option.

This examination analyzes materials, cleanroom panel installation, cleanroom HVAC compatibility, and cleanroom panel cost. It uses Deiiang™ catalogue data plus case-study data reviewed with Jason.peng, a Deiiang panel designer.

Modular vs. Traditional Cleanroom Panels

When weighing modular vs traditional cleanroom panels, the choice is not about quality. Choose the modular route for speed, changeover, and phased upgrades. Choose site-built construction where a permanent design and complicated capacity integration are required.

How the Two Cleanroom Panel Systems Differ

Modular cleanroom panels use prefabricated assemblies finished at the factory. Traditional builds are assembled from independent components on site. This produces different scheduling and design-build approACHes across cleanroom construction systems.

Modular systems rely on factory-controlled joints; traditional systems depend on labour quality during installation.

Table 1: Comparing Modular and Traditional Cleanroom Panels at the System Level

CriterionModular cleanroom panelsTraditional cleanroom panels
System typePrefabricated wall assembliesConstructed on-site wall assemblies
CompositionFactory-formed panel cores with edge detailsFraming and sheathing, site-applied finishing
FinishingPre-finished metal, HPL, powder coatedEpoxy, FRP or painted surfaces
FlexibilityHigh; install and reuseLow; modifications destroy the panels
Common usePharmaceutical, electronics, laboratory cleanroomsManufacturing cleanrooms, hospitals, permanent partitioning
CriterionModular cleanroom panelsTraditional cleanroom panels
System typePrefabricated wall assembliesConstructed on-site wall assemblies
CompositionFactory-formed panel cores with edge detailsFraming and sheathing, site-applied finishing
FinishingPre-finished metal, HPL, powder coatedEpoxy, FRP or painted surfaces
FlexibilityHigh; install and reuseLow; modifications destroy the panels
Common usePharmaceutical, electronics, laboratory cleanroomsManufacturing cleanrooms, hospitals, permanent partitioning

What Defines Modular Cleanroom Panels?

UG8Pu39ZF2E
video thumbnail

These panels are components made in a factory with mechanical parts for connections. Each panel is composed of a core, skins, and edge details used to assemble them together. Deiiang catalogue data shows a useful width of 1,150 mm and a thickness of 50–100 mm.

Deiiang hollow magnesium oxide modular panels employ a patented rib layout (ZL2004100277716). Top and bottom panels of 5 mm plus 11 ribs create 13 connections that are not aligned on a straight line. This adds flatness and load-carrying capacity.

Ceiling loading can be verified against project loads. An illustrative benchmark is a uniformly distributed load of 1,500 N/m² for a 50 mm MGO rockwool ceiling panel with 1,200 mm hanger spacing. Project-specific calculations always govern the final rating.

Table 2: Ceiling Panel Load and ffu Compatibility Benchmarks

Panel typeIllustrative design loadFFU compatibilitySupport spacing
50 mm MGO rockwool1,500 N/m²Suitable for distributed FFU grid1,200 mm hanger points
75 mm MGO rockwool1,800 N/m²Suitable for dense FFU grid1,200 mm hanger points
50 mm MGO standard1,200 N/m²Suitable for light FFU grid1,200 mm hanger points
Panel typeIllustrative design loadFFU compatibility
50 mm MGO rockwool1,500 N/m²Suitable for distributed FFU grid
75 mm MGO rockwool1,800 N/m²Suitable for dense FFU grid
50 mm MGO standard1,200 N/m²Suitable for light FFU grid

What Defines Traditional Cleanroom Panels?

Traditional cleanroom construction stud wall framing

This approach is constructed using site-built wall assembly, where metal studs or structural framing are erected first. The resulting cleanroom wall becomes a permanent part of the building rather than a removable product.

This sequence requires multiple trades on site in strict order. Framing, electrical rough-in, mechanical rough-in, sheathing, and finishing cannot overlap without rework.

A traditional 500 m² cleanroom wall assembly may take 4–6 weeks of site labour. A comparable modular cleanroom wall panel installation can complete in 2–3 weeks.


Materials, Construction, and Performance

Material choice determines cleanability, fire performance, and service life. The modular system uses factory-bonded cores that eliminate on-site variability. The site-built option depends on site-applied finishes whose quality varies with ambient conditions and applicator skill.

Table 3: Comparison of Material and Performance Standards

FactorsModular cleanroom wall panelsTraditional cleanroom wall panels
Core typesMGO, rockwool, PU, honeycombStud cavity, insulation boards, batts
Skin typesPre-coated steel, stainless steelGypsum board, cement, FRP
JointTongue-and-groove, gasketedTaped, skimmed, or sealed
Fire rating60–120 min system-testedAssembly-dependent
CleanabilitySmooth, hard surfaceCoating-dependent
FactorsModular cleanroom wall panelsTraditional cleanroom wall panels
Core typesMGO, rockwool, PU, honeycombStud cavity, insulation boards, batts
Skin typesPre-coated steel, stainless steelGypsum board, cement, FRP
JointTongue-and-groove, gasketedTaped, skimmed, or sealed
Fire rating60–120 min system-testedAssembly-dependent
CleanabilitySmooth, hard surfaceCoating-dependent

Materials and Surface Finishes

Cleanroom panel material comparison

Modular panel construction uses factory pressure to bond skins to cores. Traditional construction depends on adhesion achieved on site. Therefore delamination risk, flatness, and long-lasting appearance differ between the two.

Deiiang catalogue data lists coatings including PET colour-coated steel, galvanized plate, stainless steel, and anti-static powder coating. The electrolytic steel plate option uses 1.0–1.2 mm steel with high-voltage electrostatic powder paint. These surfaces withstand repeated cleaning with quaternary ammonium and IPA agents.

Cleaning agents to avoid on panel surfaces:

Do not use phenol solutions above 5% concentration; they can soften polyester coatings.
Do not use strong alkaline chlorinated products; they may harm aluminium edge profiles.
Avoid abrasive acidic descalers; they scratch pre-coated steel and remove gloss.

Cleanroom Wall Panels and Environmental Performance

Cleanroom panel environmental performance comparison

Wall panels must combine cleanability, leakage, fire, and acoustic properties. A panel effective in one category may be weak in another. iso 14644-3:2019 provides guidelines for leak detection [7].

Fire performance is determined by system testing rather than material datasheets alone. A rockwool panel rated for 120 minutes reaches that rating only with correct joint sealing and penetration detailing.

Deiiang catalogue data lists 120-minute fire protection for MGO rockwool panels at density 60–140 kg/m³. Standard MGO panels are rated for 60 minutes.


Cleanroom Panel Installation and Project Delivery

Two main factors differentiate modular panel installation from traditional installation. Modular panels arrive in installation sequence, so less sorting and damage occurs on site. Traditional construction requires material staging, cutting, and finishing on site.

Table 4: Comparison of Installation Stages

StageModular cleanroom panelsTraditional cleanroom panels
Site preparationFloor levelling and setting outFloor and framing layout
Primary installationPanel hanging and joint lockingStuds, substrate, and sheathing
ServicesPre-formed openingsField-cut openings
FinishingFactory finishCoating, sealing, and curing
InspectionJoint integrity inspectionSurface, seal, and adhesion inspections
CommissioningAirflow and particle countAirflow, particle count, cure verification
StageModular cleanroom panelsTraditional cleanroom panels
Site preparationFloor levelling and setting outFloor and framing layout
Primary installationPanel hanging and joint lockingStuds, substrate, and sheathing
ServicesPre-formed openingsField-cut openings
FinishingFactory finishCoating, sealing, and curing
InspectionJoint integrity inspectionSurface, seal, and adhesion inspections
CommissioningAirflow and particle countAirflow, particle count, cure verification

Installation Sequence and Trade Coordination

Cleanroom panel installation sequence workers

The sequence of cleanroom panel installation determines whether trades conflict or cooperate. The modular sequence follows a top-down, outside-in logic that progressively closes the pressure boundary. Traditional construction often installs walls before ceilings, which creates access conflicts.

A 1 mm gap at a penetration can leak roughly 0.5 m³/h at 10 Pa. Unsealed cable trays and duct collars are the dominant leakage paths. Seal every penetration using approved gaskets, collars, and fire-stop details.

Table 5: Critical Penetration Sealing Inspection Checklist

Inspection pointAcceptance evidenceRisk if missed
Cable tray entrySealed collar, fire-stop recordAir leakage, fire spread
Duct penetrationGasketed sleeve, leak testPressure loss, contamination
Pipe sleeveSealant continuity, inspection photoCondensation, particle ingress
Light recessAirtight gasket, illumination checkLeakage, glare
Door framePull-rivet spacing 300 mmDeflection, seal failure
Inspection pointAcceptance evidenceRisk if missed
Cable tray entrySealed collar, fire-stop recordAir leakage, fire spread
Duct penetrationGasketed sleeve, leak testPressure loss, contamination
Pipe sleeveSealant continuity, inspection photoCondensation, particle ingress
Light recessAirtight gasket, illumination checkLeakage, glare
Door framePull-rivet spacing 300 mmDeflection, seal failure

Quality Control, Tolerances, and Commissioning

Installation tolerance quality control

Quality control differs in timing and method. Factory inspection of modular panels checks flatness, edge squareness, and finish integrity. Traditional walls are inspected only after site application, when remediation is costly.

Acceptance evidence for modular assemblies includes factory test certification, joint leakage test records, and particle counts per iso 14644-1. Traditional wall acceptance relies on site adhesion testing, coating thickness measurement, and visual inspection.

Modular panels provide traceable acceptance evidence at handover, which shortens commissioning and supports cleanroom construction systems documentation.


Cleanroom HVAC Compatibility and Building Services

Cleanroom HVAC compatibility is not just a panel property; it is a system property derived from panel-to-HVAC interaction. Air supply, return, exhaust, and pressure control all interact with wall and ceiling panel integrity.

Deiiang catalogue data confirms iso 8 classification of standard MGO and MGO rockwool modular rooms at room level, verified by particle counting. Low panel leakage is necessary to limit fan energy while maintaining pressure cascades.

Designer's Insight from Jason.peng: thermal bridging occurs when aluminium frames meet cold ducts or cold exterior walls. Use thermal breaks at panel-to-panel joints and insulated penetration sleeves. This reduces condensation risk and stabilises the HVAC interface.

Table 6: Services Coordination Matrix

ServiceInterface requirementVerification
Supply airCeiling panel openings, FFU gridAirflow visualisation
Return airLow-wall or raised-floor grillesPressure differential
ExhaustWall penetration, sealed collarLeak test
LightingCeiling recess, airtight gasketIllumination, leak test
UtilitiesPre-formed wall sleevesSeal integrity
ServiceInterface requirementVerification
Supply airCeiling panel openings, FFU gridAirflow visualisation
Return airLow-wall or raised-floor grillesPressure differential
ExhaustWall penetration, sealed collarLeak test
LightingCeiling recess, airtight gasketIllumination, leak test
UtilitiesPre-formed wall sleevesSeal integrity

Airflow, Pressure, and Leakage Interfaces

Cleanroom airflow leakage pressure interface

Wall joints serve as pressure boundaries between classified zones. A 1 mm gap around a 3 m panel joint creates a leak that makes pressure control difficult. Modular tongue-and-groove joints with sealing gaskets minimise this risk.

At 10 Pa, a joint leaking 0.5 m³/h per linear metre loses 1.5 m³/h over 3 m. A 20 m room perimeter with unsealed joints leaks 30 m³/h. iso 14644-3:2019 provides test methods for airflow, pressure difference, and leakage [7].

Table 7: Target Values for Pressure Gradients

Zone pairTypical pressure differentialVerification method
Grade B to grade c10–15 PaPressure reading and log
Grade C to Grade D5–10 PaPressure reading and log
Grade D to corridor5–10 PaPressure reading and log
Isolator to room10–15 PaPressure reading and alarm verification
Zone pairTypical pressure differentialVerification method
Grade B to Grade C10–15 PaPressure reading and log
Grade C to Grade D5–10 PaPressure reading and log
Grade D to corridor5–10 PaPressure reading and log
Isolator to room10–15 PaPressure reading and alarm verification

Filters, Ducts, Lights, and Utility Integration

Cleanroom ceiling filter duct light integration

Coordination of filters and utility integration determines whether the ceiling panel system interferes with or supports cleanroom performance. Ceiling panels must permit FFU grids, lights, and sprinklers while maintaining structural stability.

Filter classification follows EN 1822-1:2019 and ISO 29463-1:2024 [1][2]. These standards specify EPA, HEPA, and ULPA classes by integral and local efficiency at the most penetrating particle size.

Deiiang ceiling suspension specifications use round steel hanger rods at 1,200 mm intervals, suitable for FFU ceiling systems. This spacing also protects cleanroom HVAC compatibility by limiting panel deflection under load.


Cleanroom Panel Cost and Lifecycle Economics

Cleanroom panel cost comparisons should distinguish initial material cost from actual lifecycle cost. An apparently lower initial investment can translate into a larger expense once maintenance and reconfiguration are counted.

Table 8: Lifecycle Cost Comparison

Cost typeModular cleanroom panelsTraditional cleanroom panels
Start-up costsHigher per m²Lower per m²
Labour costsLower; factory-fittedHigher; more labour-intensive
Cost of interruptionsFaster implementationMore time on site
Repair costsreplace the panelRepair coating and re-seal
Cost of changesRelocate panelsDemolish and rebuild
Disposal costsReuse or resaleLandfill and disposal
Cost typeModular cleanroom panelsTraditional cleanroom panels
Start-up costsHigher per m²Lower per m²
Labour costsLower; factory-fittedHigher; more labour-intensive
Cost of interruptionsFaster implementationMore time on site
Repair costsreplace the panelRepair coating and re-seal
Cost of changesRelocate panelsDemolish and rebuild
Disposal costsReuse or resaleLandfill and disposal

Initial Costs, Labor, and Schedule Effects

Modular versus traditional cleanroom cost comparison

The systems differ in their initial cost drivers. Modular systems carry higher initial material expenses but significantly lower labour costs. Conventional panels have lower material costs but are more labour-intensive and take longer.

A 100 m² ISO 8 modular cleanroom at USD 150/m² panel price represents USD 15,000 in materials. Installation at 25 m² per crew-day requires 4 crew-days. A conventional wall of the same area may cost USD 90/m² in materials but require 10 crew-days plus curing time.

Maintenance, Reconfiguration, and Lifecycle Value

Cleanroom lifecycle cost curve

Replacement cycles for modular wall panels typically vary from 5–8 years in pharmaceutical cleanrooms to 10–15 years in electronics cleanrooms. Conventional walls may need coating refurbishment every 3–5 years and full replacement after 15–20 years.

Reuse is the greatest benefit of a modular system. Panels removed during reconfiguration can be reinstalled in another configuration with new sealing gaskets. Industry data indicates prefabricated reconfigurable systems shorten installation time by 20–35% versus conventional systems [6].


Cleanroom Renovation, Flexibility, and Future Expansion

In retrofit projects, modular systems show distinct advantages. Modular panels can be deconstructed and reused, while traditional wall systems cannot. Phasing also allows production to continue in adjacent zones during the renovation.

A project-reported Deiiang case describes a modular ISO 8 room measuring 6 m × 5 m × 3 m (19′8″ × 16′5″ × 9′10″) with MGO rockwool panels. It was reconfigured into 10 m × 5 m × 3 m (32′10″ × 16′5″ × 9′10″).

The renovation reused 70% of the original wall panels. These figures are project-reported and should be verified against specific site conditions.

Table 9: Project-Reported Deiiang Cleanroom Renovation Metrics

MetricBeforeAfterChange
Footprint6 m × 5 m × 3 m10 m × 5 m × 3 mExpanded
Installation time10 crew-days8 crew-days20% faster
Material reuse0% reused70% wall panels reused70% reuse
Traditional estimate25 crew-daysNot applicable68% faster than traditional
MetricBefore → AfterChange
Footprint6 m × 5 m × 3 m → 10 m × 5 m × 3 mExpanded
Installation time10 crew-days → 8 crew-days20% faster
Material reuse0% reused → 70% wall panels reused70% reuse
Traditional estimate25 crew-days → not applicable68% faster than traditional

Renovation, Expansion, and Changeover

Cleanroom renovation expansion construction project

Renovation timing depends on the sequence of operations. Modular renovation follows isolation, demounting, modification, and reinstallation. Traditional methods involve demolition, disposal, and rebuilding. Modular panels support this by design.

Phasing allows half the room to remain operational while the other half is renovated. Traditional walls do not, because demolition creates dust, vibration, and access barriers that compromise adjacent classified areas.

Adaptability, Relocation, and Long-Term Facility Changes

Modular cleanroom relocation workers disassembling

Relocation ability depends on panel condition, joint type, and ceiling grid compatibility. Panels with tongue-and-groove joints and reusable gaskets relocate more easily than bonded or sealed systems.

Facilities that change more than once every 5 years should default to modular. Facilities with fixed process tools and a 15-year-plus horizon can justify traditional construction. A hybrid approach uses modular walls for changeable zones and traditional construction for permanent cores.


Standards, Validation, and Risk Management

Standards compliance is required for cleanrooms operating in regulated environments. Room classification is defined by particle counts, and test methods are defined in ISO 14644. High-efficiency filter standards appear in EN 1822-1 and ISO 29463-1.

Edition checking is essential. A specification citing EN 1822:2009 may reference superseded requirements. IEST-RP-CC001.7 describes HEPA and ULPA filter performance criteria and construction grades [11]. ASHRAE 52.2-2017 defines MERV ratings up to MERV 16 [4].

Table 10: Compliance Matrix

StandardScopePanel relevance
iso 14644-1:2015Particle concentration classificationRoom-level validation
ISO 14644-3:2019Test methodsAirflow, leak, and recovery testing
EN 1822-1:2019EPA/HEPA/ULPA classificationFilter selection
ISO 29463-1:2024High-efficiency filter classificationSupporting filter evidence
IEST-RP-CC001.7HEPA and ULPA filter provisionsFilter construction grades
ASHRAE 52.2-2017MERV ratingsGeneral ventilation filtration
StandardScopePanel relevance
ISO 14644-1:2015Particle concentration classificationRoom-level validation
ISO 14644-3:2019Test methodsAirflow, leak, and recovery testing
EN 1822-1:2019EPA/HEPA/ULPA classificationFilter selection
ISO 29463-1:2024High-efficiency filter classificationSupporting filter evidence
IEST-RP-CC001.7HEPA and ULPA filter provisionsFilter construction grades
ASHRAE 52.2-2017MERV ratingsGeneral ventilation filtration

cleanroom classification and Verification

ISO 14644 cleanroom classification

Room classification and component ratings are separate concepts. A panel may carry a fire rating and a surface finish rating. iso 8 classification of a room comes from particle counting, airflow testing, and pressure verification.

ISO 14644-1:2015 classification involves particle sampling at specified locations using a light scattering airborne particle counter [8]. ISO 14644-3:2019 provides the test methods [7]. A panel with leaking joints cannot be classified even if its surface meets cleanliness limits.

Filter Standards and Evidence Boundaries

HEPA filter standard evidence comparison

Filter standards show the limits of test scope and evidence type. EN 1822 tests at the most penetrating particle size. ISO 29463 is based on EN 1822 and enables international procurement [2].

IEST-RP-CC001.7 covers HEPA and ULPA filters for cleanrooms under ISO 14644 scope [11]. ASHRAE 52.2-2017 addresses general ventilation filtration with MERV ratings up to 16 [4].

EN 779 has been replaced by ISO 16890 for general ventilation filters [12]. MERV ratings do not substitute for HEPA classification under EN 1822 or ISO 29463.


Selection Framework and Recommendation

Takeaway: for modular vs traditional cleanroom panels, choose the modular route when speed, flexibility, and phased expansion matter most. Choose site-built construction when customization and complex structural integration are essential.

The choice of modular versus traditional cleanroom panels relies on project priorities. If speed, flexibility, and easy reconfiguration matter, the modular option is recommended. If customization and complex structural integration are essential, site-built systems suit better. There is no single winning choice.

Facilities that change cleanroom systems more often than once every five years, have tight timelines, or need phased renovation are better served by modular systems. Facilities with stable technology and permanent ceiling structures are better served by traditional systems.

Decision Criteria by Facility and Project Type

Cleanroom panel selection decision matrix

Rank the criteria by priority for the project type. Different facility types weigh schedule, cleanliness, expansion ability, services, and budget differently.

Table 11: Project Decision Scoring for Modular vs Traditional Cleanroom Panels

Decision factorModular score 1–5Traditional score 1–5
Flexibility and future changes52
Sensitivity to initial budget34
Speed of validation52
Cleanliness and accessibility44
Services and structural integration35
Decision factorModular score 1–5Traditional score 1–5
Flexibility and future changes52
Sensitivity to initial budget34
Speed of validation52
Cleanliness and accessibility44
Services and structural integration35

Pharmaceutical sterile suites value cleanliness and validation speed. Semiconductor fabs prefer vibration control and service density. Hospital pharmacies emphasise renovation phasing and cleanliness. Deiiang catalogue data covers ISO 8 modular rooms from 6 m² (64 ft² 106 in²) to 80 m² (861 ft² 126 in²).

Procurement Checklist and Specification Requirements

Cleanroom panel procurement checklist

Procurement should specify interfaces, testing, tolerances, and warranties. Ambiguous specifications cause conflicts during commissioning. For the modular option, require a demounting and reinstallation procedure. For the site-built option, require coating adhesion records and sealant compatibility data.

Table 12: Procurement Readiness Checklist for Cleanroom Panel Orders

Required informationExample specificationVerification document
Joint leaktightness limit≤0.5 m³/h per linear metre at 10 PaLeak test report
Panel flatness tolerance≤1.5 mm per 2 mFactory inspection report
Fire test records60 or 120 min ratingTest certificate
Filter ratingEN 1822-1:2019 or ISO 29463-1:2024Filter test report
Installation methodPull rivets at 300 mm, hangers at 1,200 mmMethod statement
Warranty conditions5-year coating, 10-year coreWarranty certificate
Required informationExample specificationVerification document
Joint leaktightness limit≤0.5 m³/h per linear metre at 10 PaLeak test report
Panel flatness tolerance≤1.5 mm per 2 mFactory inspection report
Fire test records60 or 120 min ratingTest certificate
Filter ratingEN 1822-1:2019 or ISO 29463-1:2024Filter test report
Installation methodPull rivets at 300 mm, hangers at 1,200 mmMethod statement
Warranty conditions5-year coating, 10-year coreWarranty certificate

Frequently Asked Questions

Are modular cleanroom panels better than traditional panels?

Neither type is universally better. The modular type allows speed, future changes, and phased renovation. The traditional type is more advantageous for permanent installations with complex structural interfaces. The best option depends on the priorities set for each project.

Which cleanroom panel system costs less?

Initial raw material outlay is usually lower for site-built walls. Over the lifecycle, the modular route usually costs less once reconfiguration and downtime are counted. Cleanroom panel cost depends on classification, size, services density, and local labour rates.

How long does cleanroom panel installation take?

Installation time depends on room size, services density, and site access. Certified crews install modular cam-lock cleanroom panels at 20–30 m² per day under favourable conditions [5]. Conventional wall panels take longer because many trades are involved and curing times apply.

Can modular panels be used for cleanroom renovation?

Yes. They are suitable for reuse projects because they can be disassembled, stored, and reassembled. Before reuse, the condition of the panels, the ceiling grid compatibility, and service isolation must be checked.

How do panels affect cleanroom HVAC compatibility?

Panels create the pressure containment that the HVAC system controls. Joint leakage, penetration sealing, and ceiling suspension integrity determine airflow balance and pressure cascades. Coordinated design and ISO 14644-3:2019 verification give reliable results.

Which standards should cleanroom panel buyers review?

Buyers should review ISO 14644-1:2015 for classification and ISO 14644-3:2019 for verification testing. For filter classification, check EN 1822-1:2019 or ISO 29463-1:2024. Filter construction grades are described in IEST-RP-CC001.7.


References

  • [1] EN 1822-1:2019, High efficiency air filters (EPA, HEPA and ULPA) — Part 1: Classification, performance testing, marking. CEN.
  • [2] ISO 29463-1:2024, High-efficiency filters and filter media for removing particles in air — Part 1: Classification, performance, testing and marking. ISO.
  • [3] iso 14644-4:2022, Cleanrooms and associated controlled environments — Part 4: Design, construction and start-up. ISO.
  • [4] ANSI/ASHRAE Standard 52.2-2017, Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size. ASHRAE.
  • [5] RaxPanel, "How Manufacturers Manage Large-Scale Clean Room Projects." Project-reported installation rates.
  • [6] IndexBox, "World Cleanroom Partition Panels — Market Analysis, Forecast, Size, Trends and Insights," 2026. Industry-reported price ranges and replacement cycles.
  • [7] ISO 14644-3:2019, Cleanrooms and associated controlled environments — Part 3: Test methods. ISO.
  • [8] ISO 14644-1:2015, Cleanrooms and associated controlled environments — Part 1: Classification of air cleanliness by particle concentration. ISO.
  • [9] Deiiang™ Cleanroom Panel Catalogue — Huijun Hollow Magnesium Oxide Panel technical data, Patent No. ZL2004100277716.
  • [10] Deiiang™ Cleanroom Panel Installation Detail Drawings — construction details for wall, ceiling, corner, door, and window assemblies.
  • [11] IEST-RP-CC001.7, HEPA and ULPA Filters. Institute of Environmental Sciences and Technology.
  • [12] ISO 16890-1:2016, Air filters for general ventilation — Part 1: Technical specifications, requirements and classification system based upon particulate matter efficiency. ISO.